Sl.No Item Name Quantity
1 AIR CONDITIONING PLANTS - Dismantling of existing plant including 2 Nos reciprocating compressor and motor, 2 nos cooling tower, 1 Nos fresh air blower, 1 Nos cement plastered AHU, 2 Nos blowers etc. Details are as per Annexure-I 1Lot
2 AIR CONDITIONING PLANTS - Design, testing, supply, installation and commissioning of factory assembled, microprocessor controlled Air-cooled, scroll chiller packages of minimum capacity of 40 TR (120000 Kcal/hr). Technical details are as per annexure-II. 1Each
3 AIR CONDITIONING PLANTS - Design, supply, installation, commissioning and testing of suitable model pump set of horizontal split case pump. The pump shall handle minimum 365 lpm of water against a head of minimum 25M. Details are as per annexure - III. 2Each
4 AIR CONDITIONING PLANTS - Supply, installation of dia 100 MS C class pipe with insulations. Details are as per annexure - IV. 100m
5 AIR CONDITIONING PLANTS - Supply, installation of dia 50 MS C class pipe with insulations (Drain Pipe). Details are as per annexure - IV. 30m
6 AIR CONDITIONING PLANTS - Supply, installation of dia 32 MS C class pipe with insulations (Expansion tank pipe). Details are as per annexure - IV. 35m
7 AIR CONDITIONING PLANTS - Supply and Installation of Dia 100 mm butterfly valve. Details are as per annexure-IV. 8Each
8 AIR CONDITIONING PLANTS - Supply and Installation of Dia 100 mm Motorized butterfly valve. Details are as per annexure-IV. 8Each
9 AIR CONDITIONING PLANTS - Supply and installation of 100 mm dia manual balancing cum flow measurement valve (Advance make or equivalent). Details are as per annexure-IV. 2Each
10 AIR CONDITIONING PLANTS - Supply and installation of 100 mm dia flexible pipe connector. Details are as per annexure-IV. 8Each
11 AIR CONDITIONING PLANTS - Supply and installation of 100 mm dia Y strainer. Details are as per annexure-IV. 2Each
12 AIR CONDITIONING PLANTS - Supply and installation of 100 mm dia non return valve. Details are as per annexure-IV. 3Each
13 AIR CONDITIONING PLANTS - Supply and installation of 80 mm dia 3 way modulating valve with motor and thermostat. Details are as per annexure-IV. 1Each
14 AIR CONDITIONING PLANTS - Supply and installation of 80 mm dia globe valve. Details are as per annexure-IV. 1Each
15 AIR CONDITIONING PLANTS - Supply and installation of 100mm dia pressure guage (with pet cock/gate valve) . Details are as per annexure-IV. 8Each
16 AIR CONDITIONING PLANTS - Supply and installation of differential pressure switch. Details are as per annexure-IV. 1Each
17 AIR CONDITIONING PLANTS - Supply and installation of dial type temperature guage. Details are as per annexure-IV. 8Each
18 AIR CONDITIONING PLANTS - Supply and installation of Automatic air Vent. Details are as per annexure-IV. 6Each
19 AIR CONDITIONING PLANTS - Supply and installation of drain plug. Details are as per annexure-IV. 6Each
20 AIR CONDITIONING PLANTS - Supply & installation of suitable GRP panel expansion tank as per attached specification of size 0.75 m x 1.0 m x 1.0m (0.75 cubic metre capacity) insulated with 40 mm thick polyurethane foam. Details are as per annexure - I. 1Each
21 AIR CONDITIONING PLANTS - Providing Automation to AC system as per annexure - I. 1Lot
22 AIR CONDITIONING PLANTS - Supply and installation of electrical panel catering to 1 nos Aircooled scroll chiller packages and 2 nos Chilled water Pumps (High side of AC system) as per annexure - V. 1Sets
23 AIR CONDITIONING PLANTS - Supply, installation and commissioning of double skin 34000 CMH clean room AHU with 100 mmwc static pressure and standby motor as per annexure-VI. 1Each
24 AIR CONDITIONING PLANTS - Supply, installation and commissioning of Fresh air double skin AHU without cooling coil 4420 CMH, 100 mmwc static pressure as per annexure VI. 1Each
25 AIR CONDITIONING PLANTS - Factory testing, Supply, and installation of Five micron filters for prefiltration of air down to 5 microns at an efficiency of 98.5% plus. Each filters shall be as size as 610 x 610 x 150 mm and as per annexure - I. 20Each
26 AIR CONDITIONING PLANTS - HEPA filters of minimum size 610 x 610 x 300 mm (inclusive of 6 mm gasket on both side) to filter 1700 cmh of air to 0.3 micron as per annexure - I. 20Each
27 AIR CONDITIONING PLANTS - Validation of 100000 class cleanroom as per annexure-I. 1Lot
28 AIR CONDITIONING PLANTS - Supply and installation of aluminium ducting (site fabricated / prefabricated) for supply and return air of 1 mm thickness as per annexure - VII. 125m2
29 AIR CONDITIONING PLANTS - Supply and installation of aluminium ducting (site fabricated/prefabricated) for supply and return air of 1.8 mm thickness as per annexure - VII. 25m2
30 AIR CONDITIONING PLANTS - Supply and fixing of nitrile rubber (closed cell) thermal insulation for supply and return air duct with minimum 19 mm thick as per annexure - I. 160m2
31 AIR CONDITIONING PLANTS - Supply, fixing, balancing and commissioning of volume control dampers in supply air duct made of extruded alluminium complete with linkage, lever, fixing arrangement etc compatible to clean room standards. 10m2
32 AIR CONDITIONING PLANTS - Supply and fixing of fresh air louver made of extruded alluminium with bird/insect screen provided with intake louver. 4m2
33 AIR CONDITIONING PLANTS - Supply and installation of duct silencer to be provided in SA and RA duct. The silencer shall be designed to attenuate noise to meet NC-50 curve in cleanrooms. 6m2
34 AIR CONDITIONING PLANTS - Supply and installation of factory fabricated motorized fire & smoke dampers with the actuators in supply and return air path as per annexxure - I. 6m2
35 AIR CONDITIONING PLANTS - Supply and installation of heating kit. The minimum capacity of heating kit shall be 33 Kw. The heating kit shall be as per annexure-I. 1Sets
36 AIR CONDITIONING PLANTS - Stainless steel pan humidifier kit of minimum 9 Kw capacity for seasonal operation as per annexure-I. 1Each
37 AIR CONDITIONING PLANTS - Supply and installation of VFD of 20 Kw capacity for clean room AHU fan speed control as per annexure - I. 1Each
38 AIR CONDITIONING PLANTS - Supply and installation of electrical panel catering to Cleanroom AHU, FA AHU etc (for low side of AC system) as per Annexure-V. 1Each
39 AIR CONDITIONING PLANTS - Civil work comprising of pedestal for 1 nos of chiller, 2 Nos of pumps and 1 Nos of cleanroom AHU and 1 Nos of Fresh air AHU as per annexure-I. 1Lot
40 AIR CONDITIONING PLANTS - Painting of all above mentined equipments as per annexure I 1Lot